The Honeywell CC-PCNT02 is a high-performance pulse counter module designed for industrial control systems. It provides accurate counting and timing functions for monitoring rotational speed, flow rates, and event occurrences in process automation environments.
Related series
Honeywell CC-PCNT02
Honeywell CC-TCNT01
Honeywell 8937-HN
Honeywell 8939-HN
Honeywell CC-TDOB01
Honeywell CC-PAIH02
Honeywell CC-PAOH01
Honeywell CC-TAIX01
Honeywell CC-TAIX11
Honeywell CC-TAOX11
Honeywell CC-TDIL01
Honeywell CC-TAOX01
Honeywell 51199947-175
Honeywell FC-BKM-0001
Honeywell FC-QPP-0002
Honeywell CC-TUIO31
Honeywell CC-TUIO41
Honeywell CC-SCMB02 51199932-200

2. Technical Characteristics
- Number of Channels: 2 independent counting channels
- Maximum Count Frequency: 1 MHz per channel
- Count Range: 0 to 4,294,967,295 (32-bit unsigned)
- Input Signal: 0-30V DC, sinking/sourcing configurable
- Power Requirements: 5V DC ±5%, 100mA max
- Operating Temperature: 0°C to 60°C (32°F to 140°F)
- Isolation: 2500Vrms channel-to-backplane
- Module Dimensions: 120mm x 80mm x 30mm
3. Functional Modes
The CC-PCNT02 supports multiple operating modes:
- Continuous Counting: Uninterrupted counting from 0 to maximum value with automatic rollover
- Preset Counting: Stops at user-defined threshold with programmable output trigger
- Rate Measurement: Calculates frequency (Hz) based on time-interval sampling
- Time Interval: Measures elapsed time between consecutive pulses
4. Configuration Parameters
| Parameter | Options | Default Setting |
|---|---|---|
| Input Type | Sinking (NPN), Sourcing (PNP) | Sinking |
| Debounce Time | 10µs, 100µs, 1ms, 10ms | 100µs |
| Count Direction | Up, Down, Up/Down (bidirectional) | Up |