Main Brands:
Bently, Triconex, Woodward, Foxboro, Westinghouse, Reliance, Schneider, Modicon, ABB, Allen-Bradley, Motorola, GE, Yaskawa, Bosch Rexroth, ACSO, YOKOGAW, NI, ICS Triplex, Kollmorgen, Mitsubishi, MOOG, Emerson, B&R, SST, ALSTOM, EPRO, HIMA, HONEYWELL prosoft, AMAT.

Wei Xiu zhu
WhatsApp:+852 5796 0986
Wechat:13395077993
Zhejiang Yiwu Beixun Automation Technology Co., Ltd
China (Zhejiang) Pilot Free Trade Zone, No. 2 Chunpai Road, Beiyuan Street, Yiwu City, Jinhua City, 7F 7059
Website:www.bxplc2.com
Email:3076784238@qq.com

The Vibrometer MPC4 200-510-SSS-1HH is a high-performance machinery protection card designed for the VM600 rack-based monitoring system. This advanced card provides continuous online monitoring and protection for critical rotating machinery in industrial environments. It utilizes state-of-the-art DSP (Digital Signal Processing) technology to deliver real-time measurement and analysis of vibration and other mechanical parameters.

Key Features

  • 4 programmable dynamic signal inputs for vibration, displacement, and other measurements
  • 2 programmable tachometer/speed inputs for rotational speed monitoring
  • Advanced DSP technology for real-time measurement and monitoring
  • Programmable wideband and narrowband filters
  • Order tracking with simultaneous amplitude and phase monitoring
  • Programmable alarm, danger setpoints, and OK values
  • Adaptive warning and danger levels based on machine speed
  • Front panel BNC connectors for easy raw signal analysis
  • 7 front panel LEDs for status and alarm indication
  • Integrated power supply for various sensor types
  • Hot-swappable design for easy maintenance
Fig. 1: Front view of MPC4 card with BNC connectors and status LEDs
Note: The MPC4 200-510-SSS-1HH is the “Standard” version of the card, as indicated by the “1” in the 11th position of the part number. This version includes VME bus functionality and supports all measurement types.
Vibrometer MPC4 200-510-SSS-1HH  Machinery Protection Card

Technical Specifications

General Specifications

Parameter Value
Model Number 200-510-SSS-1HH
Card Type Standard Version (1 = Standard)
Dimensions (W x H x D) 200 mm x 150 mm x 30 mm
Weight Approximately 1.5 kg
Protection Rating IP20
Operating Temperature -20°C to +70°C
Storage Temperature -40°C to +85°C
Humidity 0 to 95% non-condensing
Power Supply +5 V DC ±5% and ±12 V DC
Power Consumption 12.5 W (plus 1 W per sensor)

Dynamic Signal Inputs

Parameter Value
Number of Inputs 4 per MPC4 card
DC Range 0 to +20 V or 0 to -20 V
AC Range ±10 V (maximum)
Common Mode Voltage Range -50 to +50 V
CMRR >60 dB at 50 Hz
Crosstalk -72 dB
Input Impedance 200 kΩ
Current Input Range (DC) 0 to 25 mA
Current Input Range (AC) ±8 mA (maximum)
Analog AC Frequency Range (not integrated) 0.1 Hz to 10 kHz
Analog AC Frequency Range (with integration) 2.5 Hz to 10 kHz

Processing Capabilities

Parameter Value
Filtering Options High-pass, low-pass, or band-pass
LP/HP Ratio in Bandwidth 500 (maximum)
Ripple ±0.3 dB
Slope 6 to 60 dB/octave (software configurable)
Out-of-Band Attenuation >50 dB
Amplitude Accuracy ±1% of full scale
Linear Error <±1%
Equivalent Input Noise (not integrated) <200 µV RMS

Tachometer/Speed Inputs

Parameter Value
Number of Inputs 2 per MPC4 card
Input Types Proximity probes, magnetic pickups, TTL signals
Frequency Range 0.1 Hz to 25 kHz
Input Voltage TTL: 0 to 5 V
Proximity: -24 to +24 V
Speed Accuracy ±0.05% of reading
Note: The “SSS” in the part number represents the firmware version, and “HH” represents the hardware version. The “H” increments indicate major modifications that may affect product interchangeability, while “h” increments indicate minor modifications with no effect on interchangeability.

Output Connections

Connect external devices such as recorders, alarms, or control systems to the output terminals on the IOC4T card.

Communication Connections

For remote configuration and monitoring, connect the VM600 rack to a computer or network using the appropriate communication interface (RS-232, Ethernet, etc.).

Warning: When making connections, ensure that all wiring complies with local electrical codes and safety regulations. Use appropriate wire gauges and shielding for the application.

Configuration and Operation

Configuration Methods

The MPC4 card can be configured using the following methods:

VM600 MPSx Software

The primary method of configuration is through the VM600 MPSx software, which provides a comprehensive interface for setting up all parameters, alarms, and monitoring functions.

Front Panel Controls

Basic operational parameters can be monitored using the front panel LEDs, which indicate status and alarm conditions.

Remote Communication

For remote configuration, the card can be accessed through the VM600 rack’s communication interfaces using appropriate software.

Set Alarm Parameters

LED Color Status Meaning
Green Steady Normal operation, no alarms
Yellow Steady Alarm condition (warning level)
Red Steady Danger condition (shutdown level)
Red Flashing System error or malfunction
Off No power or card not properly seated
Note: For detailed information on using the VM600 MPSx software for configuration and monitoring, refer to the VM600 MPSx Software User Manual.